ibaPADU-8AI-I
Process coupling: Analog and digital inputs (HarmonizedCode:84733080, ECCN:N, LKZ:DE, AG:N)
8A+8D inputs,+/-20mA,16Bit ADCs, 1kHz - Parallel Analog Digital Unit 8 analog and 8 digital channels
This single device replaces all previous versions of current input devices. The desired current level is selected with a rotary switch. Please refer to the data sheet for more details. Technical Specifications:
Manufacturer: iba AG Input module with 8 digital and 8 analog current inputs Rugged metal case (DIN rail construction) Dimension (WxHxD): 2.1 in x 7.9 in x 5.6 in (53 mm x 200 mm x 141 mm) Fiber optic connectors with ibaNet protocol 3MBit Daisy chain of up to eight PADU devices with ibaNet protocol 3MBit via fiber optic cable Power supply: 24V DC Power consumption: typ. 4W, (max. 8W)
------
Analog inputs: Number: 8 Design: Galvanically isolated, single ended, separate ADC per channel Resolution: 16 Bit Filters: R/C low-pass 4 kHz (permanent) Input level: ±20 mA (max.) Input impedance: 50 Ohm Sample rate: 1ms /Sample Accuracy: < 0.1 % of total measuring range Electrical isolation AC 1.5kV 16-pin clamp-type terminal included in delivery
------
Digital inputs: Numbers: 8 Design: Galvanically isolated, protected against reverse polarity, single ended Input level:
- ±24 V, max. ±60 V Signal level:
- Signal level log. 0 : > -6 V; < +6 V
- Signal level log. 1 : < -10 V; > +10 V Input current: 1mA, constant 16-pin clamp-type terminal included in delivery Special Remark:
Fiber optical links to any iba component with a 3MBit technology is possible Connection to a PCMCIA-F card via RJ11 jack is possible Status:available