ibaBM-PN

Bus monitor: Data acquisition on Profinet PN
(HarmonizedCode:84733080, ECCN:N, LKZ:DE, AG:N)
Tillverkare: iba-ag
Artikelnr: 13.120000
Bus Monitor Profinet 2 Devices -
  • 2 independend internal PN-Devices for to connect 1 or 2 PROFINET drops
  • Aquiring and recording max. 1440 Bytes/PN-Device
  • Sniffing functionality without repercussions in the PROFINET network with by data gathering
  • Supports RT- (Real Time) and IRT-communication (Isochronous Real Time)
  • Supports MRP (Media Redundancy Protocol)
  • Technical data:

  • Manufacturer: iba AG
  • Power supply: DC 24 V ±10%, not stabilized,
    2-pin connector with spring terminal, included
  • Power consumption: Max. 9,6 W
    -----
    PROFINET-Interfaces:
  • Numbers: 3 (2 x PROFINET Devices for max. 2 PROFINET drops, 1 x passive Sniffer)
  • PROFINET Devices: 2 x 2-Port-Switches (2x RJ45-jacks, 10/100 Mbit/s)
  • TAP interface (passive Sniffer): 2-Port-TAP, 2x RJ45-jacks, 10/100 Mbit/s
  • Functions:
    2x PROFINET Device, shared device (max. 4 Controller),RT, IRT (>= 250µs), MRP Client
    -----
    ibaNet-Interface:
  • Number: 1 (e.g. for connection with ibaPDA)
  • ibaNet-Protocol: 32Mbit Flex
    Allows to us in parallel up to 15 devices in a ring topology, usable for data, setup and service information (e.g. updates)
  • Data transmission rate: 32 Mbit/s
  • Connection type: 2 ST connectors for fiber optic cable (62,5/125 µm) on RX and TX, max. 2000 m cable length without repeater
    -----
    Environmental conditions:
  • Cooling: Passive
  • Operating temperature: 0 °C to 50 °C
  • Storage and transportation temperature: -25 °C to 70 °C
  • Humity class acc. to DIN 40040: F
  • Protection class: IP20
  • Monting: DIN rail clamp, vertical
  • Certification:
    EMV: IEC 61326-1 ; FCC part 15 class A
  • Dimension (Width x Hight x Depth): 41 mm x 188 mm x 141 mm (incl. clamp for Din-rail mounting)
  • Special remarks:
  • Profinet connection: via drop cable (RJ45 jack)
  • For the connection with an ibaPDA-System a bidirectional fiber optic link with a FO-I/O-card, type FOB D, is required.
  • Status:available
    Kunder som köpte denna köpte också

    ibaPDA-Request-S7-DP/PN

    31.001310
    ibaPDA Request for Data: SIMATIC S7 system (HarmonizedCode:85234910, ECCN:N, LKZ:DE, AG:N)

    FO/p2-10 Patch Cable 10m

    50.102100
    Fiber optic cable (ST jacks) (HarmonizedCode:85447000, ECCN:N, LKZ:CZ, AG:N)

    Upgrade-PDA-V7-64 to PDA-V7-128

    30.770001
    Process Data Acquisition: License Extension (HarmonizedCode:85234910, ECCN:N, LKZ:DE, AG:N)

    Upgrade-PDA-V7-128 to PDA-V7-256

    30.770002
    Process Data Acquisition: License Extension (HarmonizedCode:85234910, ECCN:N, LKZ:DE, AG:N)

    Upgrade-PDA-V7-256 to PDA-V7-512

    30.770003
    Process Data Acquisition: License Extension (HarmonizedCode:85234910, ECCN:N, LKZ:DE, AG:N)